FREE TOOL · ELECTRICIANS

Ohm's LawCalculator

Enter any two of Voltage (V), Current (A), Resistance (Ω), or Power (W) — the tool instantly solves for the remaining values using V = IR and P = VI.

Four-way solverV · I · R · PUK quick reference

Ohm's Law calculator

Enter any two values — the other two calculate automatically

Tip: clear a field to let the calculator solve for it. All four values update as you type.

Enter at least two values above to calculate the remaining quantities.

Common UK values — quick reference

Standard MCB/fuse ratings at 230V single-phase: equivalent load resistance at rated current (R = V/I) and maximum connected load.

MCB / FuseVoltageLoad Resistance (Ω)Max Power (W)
6A230V38.3 Ω1,380 W
10A230V23.0 Ω2,300 W
16A230V14.4 Ω3,680 W
20A230V11.5 Ω4,600 W
32A230V7.2 Ω7,360 W
40A230V5.8 Ω9,200 W
63A230V3.65 Ω14,490 W
100A230V2.30 Ω23,000 W
Three-phase 400V: line-to-line voltage = 230V × √3 = 400V · phase-to-neutral = 230V

Next step

Turn these figures into a professional PDF quote or invoice — free, no account needed to start.

METHODOLOGY

How Ohm's Law is calculated

The four fundamental electrical quantities — voltage, current, resistance, and power — are fully determined by any two known values. This calculator applies the standard transpositions of Ohm's Law and Joule's Law.

1

Ohm's Law: V = IR

The primary relationship: Voltage (V) = Current (A) × Resistance (Ω). Transpositions give I = V/R and R = V/I. This applies directly to DC circuits and to AC circuits with purely resistive loads such as heating elements, incandescent lamps, and resistive cooking appliances.

2

Joule's Law: P = VI = I²R = V²/R

Power (W) = Voltage × Current. Substituting Ohm's Law gives the equivalent forms P = I²R (useful when V is unknown) and P = V²/R (useful when I is unknown). The calculator selects the appropriate expression based on which two quantities are known.

3

Solving order and priority

The calculator tries pairs in this order: V and I; V and R; I and R; V and P; I and P; R and P. The first pair of known non-zero values that matches a solvable case is used. All four values are displayed once a complete solution is found. Results are rounded to 5 significant figures for display clarity.

4

Limitations for AC inductive circuits

This calculator uses real (resistive) values only. For inductive loads such as motors and transformers, the actual current drawn will be higher than Ohm's Law predicts because inductive reactance adds to the circuit impedance (Z = √(R² + XL²)). Always use nameplate rated current for motor circuits and BS 7671 tables for cable sizing.

WORKED EXAMPLE

Checking a 3 kW shower circuit

An electrician needs to verify a 3 kW electric shower at 230V is drawing the expected current and check the heating element resistance. Known: V = 230V and P = 3,000W.

Voltage (V)

230 V

Power (P)

3,000 W

Current I = P/V

13.04 A

Resistance R = V²/P

17.63 Ω

Assessment outcome

13.04A — within 16A MCB

Protection adequate · Element resistance 17.6Ω · Loop impedance should be below this value

This example uses a purely resistive load. Always carry out a full inspection and test to BS 7671 before certifying any circuit.

Next step

Turn these figures into a professional PDF quote or invoice — free, no account needed to start.

FAQ

Frequently asked questions

Common questions about Ohm's Law and its application for electricians.

What is Ohm's Law?

Ohm's Law states that the current through a conductor between two points is directly proportional to the voltage across those points and inversely proportional to the resistance. Expressed as V = I × R (voltage equals current multiplied by resistance). It was formulated by German physicist Georg Ohm in 1827 and forms the foundation of all electrical circuit analysis. Every electrician uses it daily to verify circuit designs, check test results, and diagnose faults.

Why does V = IR matter for practising electricians?

Ohm's Law underpins every calculation an electrician makes on site. When you measure a voltage drop under load, you can calculate the circuit resistance. When you know the load resistance and supply voltage, you can predict the current — and therefore check whether the protective device will operate. It is also the basis for volt drop calculations under BS 7671 Appendix 4, where maximum permissible volt drop for lighting is 3% and for other circuits is 5% of the nominal supply voltage.

What is power factor and how is it different from this calculator?

Power factor is the ratio of real power (kW) to apparent power (kVA) in an AC circuit containing reactive components such as motors, transformers, or capacitors. A purely resistive load (like a heater or incandescent bulb) has a power factor of 1.0 — all apparent power is real power. Ohm's Law as shown in this calculator applies to DC circuits and purely resistive AC loads. For inductive or capacitive AC loads you need impedance (Z = V/I) rather than resistance, which adds a phase angle component.

What is the difference between resistance and impedance?

Resistance (Ω) is the opposition to current flow in DC circuits and purely resistive AC circuits. Impedance (Z, also in Ω) is the total opposition in AC circuits and includes resistance (R), inductive reactance (XL = 2πfL) and capacitive reactance (XC = 1/(2πfC)). For a motor, transformer, or any inductive load the impedance will be higher than the measured DC resistance. For fault calculations under BS 7671, electricians use impedance figures from IEE Wiring Regulations Appendix 14 rather than DC resistance.

What is 230V single-phase and 400V three-phase in the UK?

UK mains supply is 230V AC single-phase (between live and neutral) and 400V AC three-phase (between any two line conductors, formerly called 415V before harmonisation in 1995). Single-phase is used for domestic supplies and most light commercial loads. Three-phase is used for industrial machinery, commercial premises, EV charge points above 7kW, and any load over approximately 7–10kW where balanced loading is important. The phase-to-neutral voltage on three-phase is also 230V — the 400V is the line-to-line voltage, which is 230 × √3.

How do I measure resistance with a multimeter?

Set your multimeter to the resistance (Ω) function. Ensure the circuit is ISOLATED — dead and proved dead with an approved voltage indicator before connecting. Connect the test leads across the component or cable run you want to measure. For cable continuity, short the far end and measure from the near end; for earth loop path resistance, use a dedicated loop impedance tester rather than a standard multimeter. When measuring in-circuit, be aware that parallel paths will give a lower reading than the true component resistance. Always zero the leads first by touching them together and noting the residual lead resistance.

What are common mistakes when reading volt drop?

The most common mistakes are: (1) measuring voltage at the board rather than at the load, so the meter sees supply voltage not the actual volt drop; (2) forgetting that volt drop compounds over a long circuit — each metre of cable adds resistance; (3) using the wrong temperature coefficient — cable resistance increases approximately 0.4% per °C above 20°C, so a cable at 70°C operating temperature has about 20% more resistance than its cold value; (4) ignoring the return path — volt drop is calculated over the full circuit length (go and return), not just the outgoing cable.