FREE TOOL · PLUMBERS

Pipe SizingCalculator

Size domestic water supply pipes to BS EN 806 and CIBSE Guide G — enter your flow rate, pipe run, and fittings to get the minimum recommended pipe diameter with pressure drop and velocity checks.

BS EN 806 / BS 8558Pressure drop checkVelocity limit flag

Pipe sizing calculator

Pipe run details

Typical domestic: 8–20 L/min

+0.5m equivalent each

+1.0m equivalent each

2.0 bar
0.5 bar (gravity)6 bar (mains max)

Typical UK mains: 1.5–4 bar. Measure at stopcock with a pressure gauge for accuracy.

Sizing results

Recommended Size

22mm

Minimum pipe diameter

Pressure Drop

0.148 bar

At 22mm

Velocity at recommended size0.64 m/s
Total equivalent length18.5 m
Equivalent length breakdown15m pipe + 1.5m bends + 2.0m tees
StatusOK

All pipe sizes — comparison

SizePressure dropVelocityVerdict
15mm0.833 bar1.58 m/sHigh ΔP
22mm ✓0.148 bar0.64 m/sOK
28mm0.046 bar0.39 m/sOK
35mm0.017 bar0.25 m/sOK
42mm0.007 bar0.17 m/sOK

Next step

Turn these figures into a professional PDF quote or invoice — free, no account needed to start.

METHODOLOGY

How pipe sizing is calculated

This calculator uses the equivalent length method recommended by CIBSE Guide G and BS EN 806-3 for sizing domestic water supply pipework.

1

Equivalent length calculation

Total equivalent length = actual pipe length + (bends × 0.5m) + (tees × 1.0m). This accounts for increased turbulence and friction at fittings — a common source of error when pipes are undersized. Stop valves and gate valves add a further 2–4m equivalent each and should be added manually to the fittings count.

2

Pressure drop lookup (BS EN 806 chart method)

Pressure drop per metre (mbar/m) is obtained from a simplified version of the BS EN 806 design charts based on the Darcy-Weisbach friction equation. The table covers flow rates of 8–30 L/min and pipe sizes from 15mm to 42mm copper. Values are linearly interpolated for intermediate flow rates. For CPVC and PEX, a material correction factor is applied to account for rougher bore.

3

Total pressure drop

Total pressure drop (bar) = (mbar/m × equivalent length) ÷ 1,000. A value at or below 0.5 bar is the typical design target for a domestic circuit — this leaves sufficient residual pressure at the draw-off point. For systems fed from cold water storage cisterns (gravity-fed), available pressure is typically 0.1 bar per metre of head.

4

Velocity check

Flow velocity = volumetric flow rate (m³/s) ÷ pipe internal cross-sectional area (π × (d/2)²). CIBSE Guide G recommends a maximum of 2.5 m/s for domestic copper pipework. The calculator flags any size exceeding this limit, as high velocity causes erosion corrosion — particularly at bends — and noise complaints. Reference: BS EN 806-3:2006 and CIBSE Guide G.

WORKED EXAMPLE

Sizing a cold water supply to a new en-suite in Leeds

Mike is a plumber in Leeds running a 22m cold water supply from the rising main to a new en-suite. The run has 5 bends and 3 tees. Design flow rate is 12 L/min. Mains pressure is 2.5 bar.

Pipe length

22m

Equivalent length

22 + 2.5 + 3.0 = 27.5m

Drop/m at 22mm

8 mbar/m

Total drop at 22mm

220 mbar = 0.22 bar

Recommended size

22mm copper

0.22 bar drop · well within 0.5 bar limit · velocity 0.64 m/s ✓

This is illustrative. Always verify mains pressure with a gauge and refer to BS EN 806 and BS 8558 for final design sign-off.

STOP UNDERCHARGING

Now charge your worth — and keep your time.

You've sized the pipe. Now turn it into a professional quote in minutes. Sleepless Tradesman quotes, invoices and plans every job — for free, no card required.

No card · No commitment · Cancel anytime

FAQ

Frequently asked questions

Common questions about pipe sizing and water supply design.

What does BS EN 806 say about pipe sizing?

BS EN 806-3 (Design for Water Supply) is the UK standard governing domestic hot and cold water installations. It requires pipe sizes to maintain adequate flow and pressure at all draw-off points while keeping velocity within limits that prevent erosion and noise. The standard is supplemented by BS 8558 and CIBSE Guide G, which provide detailed design charts. The equivalent length method used in this calculator is the approach endorsed by these standards.

What are the velocity limits for copper pipe in the UK?

CIBSE Guide G and BS EN 806 recommend keeping velocity in copper pipes below 2.0 m/s for hot water circuits and below 3.0 m/s for cold water under normal conditions. Many engineers use 2.5 m/s as a working limit for both. Exceeding this causes erosion corrosion — particularly at bends and fittings — creates noise, and can void manufacturer warranties on valves and cylinders. For microbore (10mm) pipe the limit is typically 1.5 m/s.

What is the flow rate difference between 15mm and 22mm copper pipe?

At a typical domestic operating pressure of 2 bar, a 15mm copper pipe (12.7mm internal diameter) carries approximately 14–18 L/min before velocity limits are breached. A 22mm pipe (20mm internal diameter) handles 30–40 L/min comfortably. The internal bore area of 22mm is nearly 2.5 times larger than 15mm. Most basin taps and shower valves specify a minimum 15mm supply; bath taps and combination showers generally require 22mm.

How do I calculate pressure drop in a domestic pipe run?

The simplified Darcy-Weisbach approach (CIBSE Guide G) has three steps: (1) Calculate the equivalent length by adding actual pipe length to fitting resistances — each 90° bend adds ~0.5m, each tee junction adds ~1.0m. (2) Find the pressure drop per metre for your pipe diameter at your design flow rate from BS EN 806 design charts. (3) Multiply drop per metre by equivalent length to get total drop in mbar. For domestic circuits, a total drop of 0.5 bar or less is the standard design target.

How much do bends and fittings affect pipe flow?

Fittings account for 20–50% of total pressure loss in a domestic pipe run. Each 90° elbow on 22mm copper has an equivalent length of roughly 0.5–1.0m; a tee junction drawing from the side branch adds 1.0–2.0m. Stop valves add 2–4m equivalent length each when half-open. Always count all fittings when sizing pipe — ignoring them produces an under-designed system that underperforms at the tap.

Does hot water pipe sizing differ from cold water?

The sizing method is the same — the flow rate and equivalent length method applies to both. Hot water circuits have additional considerations: pipe material must be rated for sustained temperatures above 65°C (copper and CPVC are fine; PEX must be rated to at least 82°C for primary circuits); thermal expansion must be accommodated with expansion loops or flexible connections on longer runs; and insulation requirements under Part L of Building Regulations and BS 5422 apply to all hot water distribution pipes in habitable buildings.

What are the UK pipe insulation requirements?

Under Part L of the Building Regulations (England) and equivalent devolved requirements, all hot water distribution pipes must be insulated to BS 5422 levels wherever they run through unheated spaces (loft, garage, external void). For a 22mm copper pipe in an unheated space, 25mm thick class O insulation (e.g., Armaflex) is typically required. Cold water pipes in unheated spaces should be insulated against freezing, with minimum 25mm insulation and a minimum pipe depth below ground of 750mm for external runs per WRAS guidance.