FREE TOOL · ELECTRICIANS
Apply all four BS 7671 derating factors — ambient temperature, grouping, thermal insulation and fuse type — to find the minimum cable Iz rating required for your circuit.
Combined Factor Ct
1.000
Ca × Cg × Ci × Cc
Min Required Iz
20.0 A
tabulated cable rating needed
Select a cable size whose tabulated Iz (from BS 7671 Appendix 4 or manufacturer data) equals or exceeds this value.
Next step
Turn these figures into a professional PDF quote or invoice — free, no account needed to start.
BS 7671 Appendix 4 provides correction factors that adjust the tabulated current-carrying capacity of cables for non-standard installation conditions. All four factors are applied simultaneously by multiplication.
Cable ratings are published at a reference ambient temperature of 30°C. For 70°C (PVC) cables, Ca ranges from 1.03 at 25°C down to 0.61 at 55°C. For 90°C XLPE cables, which have a higher headroom, the correction is less severe. Factors come from BS 7671 Table 4B1. A loft in summer can reach 50°C, reducing a 70°C cable rating to 71% of its nominal value.
Cables grouped in conduit, trunking, or touching on a cable tray cannot radiate heat freely. BS 7671 Table 4C1 provides grouping factors based on the number of cables in the group. The factors assume all cables in the group carry full load simultaneously (pessimistic). Where diversity is guaranteed (e.g. single-phase circuits that cannot all be fully loaded simultaneously), a less onerous group factor can be applied — but only with justification on the installation schedule.
Thermal insulation prevents cable heat dissipation and is the most severe single derating factor. A cable totally enclosed in insulation carries only 50% of its clipped-to-surface rating. Cable touching insulation on one side: 75%. BS 7671 Regulation 523.9 states that cables enclosed in thermal insulation must be rated accordingly. In practice, cables in loft insulation should be routed above the insulation level, or a substantially larger cable should be specified.
Semi-enclosed rewirable fuses (BS 3036) have a higher pre-arcing I²t than HRC fuses or MCBs for the same rated current. This means they let more energy through before operating, and the cable must be uprated to compensate. BS 7671 Regulation 433.1.1 requires a correction factor Cc = 0.725 when BS 3036 fuses are used. This means the cable must carry 38% more current than the circuit design current. Modern consumer units no longer use BS 3036 fuses — this factor applies only to older rewirable fuse boards.
WORKED EXAMPLE
A 20A ring final circuit (PVC cable) runs through a section of loft fully packed with mineral wool insulation (Ca = 50°C ambient), with 4 cables grouped together in the same area. Protected by a standard MCB. What minimum tabulated cable rating is required?
Design current Id
20 A
Ca (50°C, 70°C cable)
0.71
Cg (4 cables grouped)
0.65
Ci (totally surrounded)
0.50
Combined Ct
0.231
Min Iz required
86.6 A
Solution
Route cables above insulation
86.6A tabulated Iz for a 20A circuit is impractical — resolve by improving installation method
When derating produces an unrealistic cable size, the answer is always to improve the installation method: reduce grouping, route out of insulation, reduce ambient temperature, or use 90°C XLPE cable. Refer to BS 7671 18th Edition Appendix 4 and the IET On-Site Guide.
Verify BS 7671 Zs compliance for any MCB or fuse type.
Calculate prospective fault current in kA and verify breaking capacity.
Size your earth conductor using BS 7671 Table 54.7 or the adiabatic equation.
Calculate household electricity consumption and consumer unit upgrade needs.
Calculate income tax, NI and monthly set-aside for 2024/25.
Log business miles and expenses to maximise your tax deduction.
Find the right hourly rate for electricians by region.
See exactly how much you make on any job after all costs.
Calculate total labour cost including NI and travel.
Set your sell price and see the true margin on materials.
STOP UNDERCHARGING
You've selected the right cable size. Now turn it into a professional quote in minutes. Sleepless Tradesman quotes, invoices and plans every job — for free, no card required.
No card · No commitment · Cancel anytime
Common questions about cable derating and BS 7671 correction factors.
Cable derating is the process of reducing the rated current-carrying capacity (Iz) of a cable to account for installation conditions that increase its operating temperature. Cables are rated at specific reference conditions — typically 30°C ambient, single cable clipped to a surface, no surrounding insulation. When any of these conditions are more onerous (higher temperature, multiple cables grouped together, cables buried in insulation), the cable cannot dissipate heat as effectively and must be operated at a lower current to avoid overheating the insulation, which can cause fire or premature failure.
Thermal insulation dramatically reduces cable current-carrying capacity because it prevents the cable from losing heat to its surroundings. A cable totally surrounded by thermal insulation (e.g. embedded in mineral wool in a wall or ceiling) must be derated to 50% of its clipped-to-surface rating (Ci = 0.5). A cable touching insulation on one side is derated to 75% (Ci = 0.75). This is why cables in loft insulation must be rated substantially higher than the circuit design current — or better, run in conduit above the insulation level. BS 7671 Regulation 523.9 specifically addresses thermal insulation.
Cables running through loft insulation are subject to the thermal insulation correction factor (Ci). If the cable is totally enclosed in the insulation, Ci = 0.5, meaning the cable must have a tabulated current rating at least twice the design current. The practical options are: (1) route cables above the insulation level and clip to rafters; (2) use a substantially larger cable size to compensate; (3) run cables in conduit that is itself above the insulation level. The IET On-Site Guide provides detailed guidance on loft cable installations. Never lay cables directly in or under insulation without applying the derating factor.
When multiple cables are grouped in trunking, conduit, or run alongside each other on a cable tray, they restrict each other's ability to dissipate heat. The grouping factor Cg (BS 7671 Table 4C1) reduces the current rating accordingly. Two cables together: Cg = 0.80; three cables: 0.70; five cables: 0.60; ten cables: 0.48; twenty cables: 0.38. In practice, electricians should spread circuits across multiple trunkings or tiers rather than running all cables through a single duct, both to improve current ratings and to allow for future circuit additions.
The ambient temperature correction factor (Ca) adjusts the cable rating for environments hotter or colder than the reference temperature of 30°C (for 70°C cables) or 30°C (for 90°C XLPE cables). In most UK domestic installations, 30°C is a reasonable assumption and Ca = 1.0. However, in plant rooms, commercial kitchens, loft spaces in summer, or industrial environments, ambient temperatures of 40–55°C are common and can significantly derate the cable. Always survey the actual installation environment — a cable near a boiler or in a hot ceiling void may be in an ambient of 50°C+ without any obvious indication.
The combined derating factor Ct = Ca × Cg × Ci × Cc. When multiple derating factors apply simultaneously, they multiply and can result in a very low combined factor. A cable at 45°C ambient (Ca = 0.79), grouped with 5 other cables (Cg = 0.60), in thermal insulation on one side (Ci = 0.75), and protected by a BS 3036 fuse (Cc = 0.725) has a combined Ct of 0.79 × 0.60 × 0.75 × 0.725 = 0.258. The cable must then be rated at almost 4× the design current. Combined Ct below 0.5 should trigger a review of the installation method.
BS 7671 (18th Edition) derating factors are: ambient temperature Ca — Table 4B1 (Appendix 4); grouping Cg — Table 4C1; thermal insulation Ci — Regulation 523.9 and Appendix 4; BS 3036 semi-enclosed fuse correction Cc = 0.725 — Regulation 433.1.1 note. The combined correction is applied to the tabulated current-carrying capacity (Iz) from the cable manufacturer or BS 7671 Appendix 4 tables. The final requirement is that the cable's tabulated Iz ≥ (design current Id) / (Ca × Cg × Ci × Cc).