FREE TOOL · ELECTRICIANS

Prospective FaultCurrent (kA)

Calculate PSCC in kA and verify your protective devices have adequate breaking capacity. Works for single-phase and three-phase supplies — enter Ze and get an instant result.

Single & three-phase6kA / 10kA checkBS 7671 Reg 536.4

Prospective fault current calculator

Supply details

Measure at the distribution board origin. Typical TN-C-S: 0.15–0.40Ω.

Enter 0 for measurement at the board origin.

Fault current result

Prospective Fault Current

0.657 kA

657 A

Min Breaking Capacity

3kA

required for MCBs / fuses

Standard 6kA MCBs are adequate

PFC of 0.66kA is within the 6kA MCB breaking capacity rating for this location.

Supply voltage230V (single-phase)
Ze (external impedance)0.350 Ω
Cable resistance R1+R20.0 mΩ
Total Zs0.350 Ω
PFC = V ÷ Zs657 A
PFC in kA0.657 kA

Quick reference: Ze vs PFC (single-phase 230V)

Ze = 0.1Ω2.30 kA
Ze = 0.2Ω1.15 kA
Ze = 0.35Ω0.66 kA
Ze = 0.5Ω0.46 kA
Ze = 0.8Ω0.29 kA
Ze = 1Ω0.23 kA

Next step

Turn these figures into a professional PDF quote or invoice — free, no account needed to start.

METHODOLOGY

How PFC is calculated

Prospective fault current is a fundamental electrical safety calculation required by BS 7671 Regulation 536.4.1. The method follows standard UK practice for domestic and commercial installations.

1

Single-phase PFC formula

For single-phase installations: PFC = 230V ÷ Zs, where Zs is the total loop impedance at the point of measurement. At the board origin (Zs = Ze), this gives the maximum PFC for the whole installation. For circuits, add the cable resistance R1+R2 to Ze. The result in amps is divided by 1,000 to express in kA for comparison with device breaking capacity ratings.

2

Three-phase PFC formula

For three-phase installations the bolted line-to-line fault current is 400V ÷ Zs. This is the worst-case fault at the point of measurement. Line-to-neutral faults use 230V ÷ Zs. Three-phase installations near the distribution transformer typically have lower Zs and therefore higher PFC than single-phase supplies served over the same cable run — this is why industrial switchgear often has higher breaking capacity ratings.

3

Breaking capacity assessment

BS 7671 Regulation 536.4.1.1 requires the rated short-circuit capacity of every protective device (Icc or Ics) to be not less than the prospective fault current at the point of installation. Standard domestic MCBs are rated 6kA. Industrial MCBs are typically 10kA. Where PFC exceeds 6kA, 10kA-rated MCBs or current-limiting HRC fuses (BS 88-2) must be used. Where PFC exceeds 10kA, consult the manufacturer's data for higher-capacity switchgear.

4

Cable resistance contribution

Adding cable resistance (R1+R2) reduces the PFC at the far end of a circuit compared to the board origin. This is why PFC is highest at the main distribution board and decreases along the circuit. For sub-main cables and distribution circuits, always calculate PFC at each board or sub-board to verify that all devices at that level have adequate breaking capacity.

WORKED EXAMPLE

Commercial unit distribution board — three-phase supply, Ze = 0.08Ω

An electrician is installing a sub-distribution board in a commercial unit fed by a 25mm² three-phase sub-main, 15m from the main LV board. Ze at the main board is 0.08Ω. What breaking capacity is required for MCBs in the sub-board?

Ze at main board

0.08 Ω

Sub-main R1+R2 (25mm², 15m)

20.7 mΩ

Zs at sub-board

0.101 Ω

PFC (400V ÷ Zs)

3.96 kA

Standard 6kA MCBs

Adequate

Min. breaking capacity

6kA

Result

3.96 kA — 6kA MCBs OK

Sub-main resistance reduces PFC enough that standard 6kA MCBs are compliant

Always record the measured PSCC on the distribution board schedule and EIC. Where Ze is lower than 0.04Ω (near a large transformer), check PFC at the main board origin as well.

STOP UNDERCHARGING

Now charge your worth — and keep your time.

You've verified your fault current. Now turn it into a professional quote in minutes. Sleepless Tradesman quotes, invoices and plans every job — for free, no card required.

No card · No commitment · Cancel anytime

FAQ

Frequently asked questions

Common questions about prospective fault current and breaking capacity.

What is prospective fault current (PFC)?

Prospective fault current (PFC), also called prospective short-circuit current (PSCC), is the maximum current that can flow through a circuit under fault conditions — either a short circuit between live conductors or an earth fault. It is calculated by dividing the supply voltage by the total circuit impedance (Zs). PFC determines the minimum breaking capacity that protective devices (MCBs, fuses) must have. If the fault current exceeds the breaking capacity, the device may fail catastrophically rather than safely interrupting the fault.

What is the difference between PFC and Icc (short-circuit current)?

PFC (prospective fault current) and Icc (rated short-circuit making capacity) refer to the same fundamental concept — the available fault current at a point in the installation. PFC is the quantity you calculate and measure on site; Icc (or Ics) is the rated value stamped on the protective device that must equal or exceed the measured PFC. BS 7671 Regulation 536.4.1 requires that every protective device has a rated short-circuit capacity not less than the prospective fault current at the point of installation.

Why do MCBs have 6kA and 10kA breaking capacity ratings?

The 6kA rating covers the vast majority of domestic and commercial final circuits where the total loop impedance is high enough to limit fault current below 6,000A. Most UK domestic TN-C-S installations have Ze around 0.2–0.4Ω, giving PFC of 575–1,150A at the board — far below 6kA. However, at the origin of the installation (the main board), with very low Ze (0.05–0.1Ω), PFC can approach or exceed 2,300A and may reach 6kA+ at the DNO cut-out. Industrial premises near the local transformer can have PFC exceeding 10kA, requiring 10kA or higher rated devices.

When should I specify 10kA MCBs instead of 6kA?

Specify 10kA MCBs when the measured or calculated PFC at the distribution board exceeds 6,000A. This typically occurs: in commercial or industrial premises close to the local distribution transformer; in large residential blocks with a short incoming supply cable and low external impedance; at the main distribution board of large installations. A Ze measurement at the origin below 0.04Ω (230V ÷ 6,000A) suggests 10kA MCBs may be required. When in doubt, the 10kA type can always replace a 6kA — it provides extra protection at minimal additional cost.

How do I measure PSCC on site?

Prospective short-circuit current is measured using a loop impedance tester set to measure at the line-to-line or line-to-neutral terminals (not line-to-earth). The tester measures the loop impedance and calculates the prospective current. For a single-phase supply, PFC = 230V ÷ Zs; for three-phase, the line-to-line PFC = 400V ÷ Zs. The measured PFC must not exceed the breaking capacity of the installed protective devices. This measurement should be taken at the incoming terminals of each distribution board and recorded on the installation certificate (EIC) or condition report (EICR).

How does PFC relate to ring final circuits?

A ring final circuit has a lower loop impedance than a radial circuit because current can flow both ways around the ring. The mid-point of the ring (the point furthest from the board) has the lowest fault current, but the board end has the highest. For ring circuits, the prospective fault current at the board end is typically dominated by the Ze and the incoming supply impedance rather than the cable. The PSCC at the socket-outlet with the lowest impedance (closest to the board) should be checked against the MCB's breaking capacity.