FREE TOOL · ELECTRICIANS
Calculate cable fill percentage per BS 7671, check compliance with the 45% fill rule, and find the maximum cables for your conduit — single-core, T&E, and three-core.
Conduit fill
39.6%
✓ Within 45% limit
Max cables at 45%
4
cables of this size/type
Conduit internal CSA
346
mm² (25mm bore)
Maximum number of single-core PVC cables per conduit size and conductor area.
| Conduit | 1mm² | 1.5mm² | 2.5mm² | 4mm² | 6mm² | 10mm² |
|---|---|---|---|---|---|---|
| 16mm | 2 | 1 | 1 | 1 | 0 | 0 |
| 20mm | 4 | 3 | 2 | 1 | 1 | 0 |
| 25mm | 7 | 5 | 4 | 3 | 2 | 1 |
| 32mm | 12 | 9 | 7 | 5 | 4 | 2 |
| 40mm | 19 | 15 | 11 | 8 | 6 | 4 |
| 50mm | 29 | 23 | 18 | 13 | 10 | 6 |
| 63mm | 48 | 39 | 30 | 22 | 16 | 11 |
Highlighted cell = your current selection. Values for single-core PVC cable; T&E and three-core give lower maximums due to larger OD.
Next step
Turn these figures into a professional PDF quote or invoice — free, no account needed to start.
Conduit fill is a comparison of the total cable cross-sectional area against the conduit's internal bore area, expressed as a percentage. The 45% limit per BS 7671 ensures cables can be drawn and replaced without damage.
For a circular conduit, the internal cross-sectional area = π × (d/2)², where d is the internal diameter in mm. Standard metric conduit sizes (16, 20, 25, 32, 40, 50, 63mm) have specified internal diameters. The internal areas used in this calculator are: 16mm = 113mm², 20mm = 201mm², 25mm = 346mm², 32mm = 572mm², 40mm = 907mm², 50mm = 1,385mm², 63mm = 2,290mm².
Single-core cable area = π × (OD/2)², using approximate overall diameters from standard PVC cable tables (e.g. 2.5mm² single-core ≈ 6.6mm OD, giving 34.2mm² area). For twin and earth cable, the calculator uses an elliptical area approximation: π × (width/2) × (height/2) — this accounts for the flat cross-section shape. Three-core cable adds approximately 10% to the equivalent OD compared to single-core.
Fill % = (total cable area ÷ conduit internal area) × 100. The BS 7671 limit for multiple cables is 45%. This is enforced to ensure cables can be drawn through and replaced without excessive pulling force that would damage insulation. The calculator also shows the maximum whole number of cables that fit within 45%, calculated as floor(conduit area × 0.45 ÷ cable area).
Meeting the 45% fill rule does not automatically mean the cables are correctly rated for their loads. BS 7671 Table 4C1 requires grouping correction factors to be applied to the current-carrying capacity of cables sharing a conduit: two circuits (Cg = 0.80), three circuits (Cg = 0.70), four circuits (Cg = 0.65), five circuits (Cg = 0.60), six or more circuits (Cg = 0.57). Always verify cable selection after applying these factors.
WORKED EXAMPLE
An electrician is running six 2.5mm² single-core PVC cables through a 20mm conduit. He needs to check whether this exceeds the 45% fill rule.
20mm conduit CSA
201 mm²
2.5mm² cable OD 6.6mm → area
34.2 mm²
6 cables total area
205 mm²
Fill = 205 ÷ 201 × 100
102% ✗
Assessment outcome
Upsize to 32mm conduit
32mm conduit (572mm²) gives 35.9% fill for 6 cables — compliant and easy to draw
Cable OD values are approximate. Always verify against the actual cable manufacturer's data sheet before finalising conduit selection.
Calculate household electricity consumption and consumer unit upgrade needs.
Check volt drop compliance across cable runs per BS 7671.
Select the correct cable size for current-carrying capacity and volt drop.
Calculate the right BTU and kW capacity for any room.
Calculate your income tax, NI and monthly set-aside for 2024/25.
Set your overhead recovery rate and target net margin.
Calculate true job cost including labour, materials, and overheads.
Solve for V, I, R, and P — enter any two values.
Convert between kW, kVA, and amps for single and three-phase.
Calculate after-diversity maximum demand for consumer unit sizing.
Next step
Turn these figures into a professional PDF quote or invoice — free, no account needed to start.
Common questions about conduit fill, BS 7671 rules, and cable derating.
BS 7671 (18th Edition Wiring Regulations) limits the total cross-sectional area of cables inside a conduit to 45% of the conduit's internal cross-sectional area. This limit applies where cables need to be drawn in or replaced after installation — it ensures enough room to pull cables through without damaging their insulation. The 45% rule is for three or more cables; for two cables the limit is 30%, and for a single cable it is 53% of the conduit bore. This calculator uses the 45% limit as the standard for multiple cables.
Cables generate heat when carrying current (I²R losses). When cables are bunched inside a conduit, their combined heat cannot dissipate as efficiently as cables clipped singly to a wall. BS 7671 requires derating of current-carrying capacity when cables are grouped — typically reducing the rated capacity by 0.6–0.8 for common grouping arrangements (Appendix 4, Table 4C1). Overfilled conduits both reduce mechanical protection (more force needed to pull) and increase thermal stress on insulation, shortening cable life.
Yes — BS 7671 permits mixed cable sizes in the same conduit, provided the total cable area still complies with the 45% fill rule. However, mixing sizes creates practical problems: different cables have different pulling tensions, so the smaller cables may be damaged during installation. Grouping derating must be applied to all cables collectively, which often means the smaller cables become the limiting factor. In practice, electricians often prefer to run separate conduits for significantly different cable sizes.
Conduit fill is calculated as a percentage of the conduit's circular cross-sectional area, with a 45% limit. Trunking fill is calculated as a percentage of the trunking's rectangular cross-sectional area, but the permitted fill percentage differs: BS 7671 Table 5A gives space factors for trunking depending on the number of cables. For trunking containing single-core cables, the fill factor is typically 45% for three or more circuits, the same as conduit. However, trunking is generally easier to fill and change than conduit because it has removable covers rather than requiring cables to be drawn through.
Cable derating is the reduction of a cable's current-carrying capacity (Iz) when it is installed in conditions worse than the BS 7671 reference method (typically single cable in free air or clipped to a surface). When multiple cables share a conduit, the grouping correction factor (Cg) from BS 7671 Table 4C1 applies. For example, two circuits in conduit: Cg = 0.8 (80% of the single-cable rating). Three circuits: Cg = 0.7. Four circuits: Cg = 0.65. Six or more: Cg = 0.57. These factors reduce the maximum permissible current and therefore the maximum load that can be connected.
BS 7671 Section 522 covers protection against mechanical damage and conduit installation. Key requirements: conduit internal diameter must be at least 1.5 times the outside diameter of the cable with the largest diameter; conduit ends must be reamed smooth to prevent cable damage; conduit must be installed with draw-in boxes at sufficient intervals for pulling (typically every 5–8 metres on a straight run or after two 90° bends); conduit must be of suitable type for the environment (PVC conduit is not suitable for temperatures above 60°C or where mechanical impact is likely — use steel conduit); all joints must be waterproof if the conduit is installed in a damp location.