FREE TOOL · ELECTRICIANS

Conduit FillCalculator

Calculate cable fill percentage per BS 7671, check compliance with the 45% fill rule, and find the maximum cables for your conduit — single-core, T&E, and three-core.

45% fill rule check16–63mm conduitAll cable types

Conduit fill calculator

Conduit and cable details

4
120

Fill calculation result

Conduit fill

39.6%

✓ Within 45% limit

Max cables at 45%

4

cables of this size/type

Conduit internal CSA

346

mm² (25mm bore)

Conduit internal area346 mm²
Cable cross-section area (each)34.2 mm²
Total cable area136.8 mm²
45% fill limit156 mm²
Current fill39.6%

Quick reference — max single-core cables at 45% fill

Maximum number of single-core PVC cables per conduit size and conductor area.

Conduit1mm²1.5mm²2.5mm²4mm²6mm²10mm²
16mm211100
20mm432110
25mm754321
32mm1297542
40mm191511864
50mm29231813106
63mm483930221611

Highlighted cell = your current selection. Values for single-core PVC cable; T&E and three-core give lower maximums due to larger OD.

Next step

Turn these figures into a professional PDF quote or invoice — free, no account needed to start.

METHODOLOGY

How conduit fill is calculated

Conduit fill is a comparison of the total cable cross-sectional area against the conduit's internal bore area, expressed as a percentage. The 45% limit per BS 7671 ensures cables can be drawn and replaced without damage.

1

Conduit internal CSA

For a circular conduit, the internal cross-sectional area = π × (d/2)², where d is the internal diameter in mm. Standard metric conduit sizes (16, 20, 25, 32, 40, 50, 63mm) have specified internal diameters. The internal areas used in this calculator are: 16mm = 113mm², 20mm = 201mm², 25mm = 346mm², 32mm = 572mm², 40mm = 907mm², 50mm = 1,385mm², 63mm = 2,290mm².

2

Cable cross-section area

Single-core cable area = π × (OD/2)², using approximate overall diameters from standard PVC cable tables (e.g. 2.5mm² single-core ≈ 6.6mm OD, giving 34.2mm² area). For twin and earth cable, the calculator uses an elliptical area approximation: π × (width/2) × (height/2) — this accounts for the flat cross-section shape. Three-core cable adds approximately 10% to the equivalent OD compared to single-core.

3

Fill percentage and 45% limit

Fill % = (total cable area ÷ conduit internal area) × 100. The BS 7671 limit for multiple cables is 45%. This is enforced to ensure cables can be drawn through and replaced without excessive pulling force that would damage insulation. The calculator also shows the maximum whole number of cables that fit within 45%, calculated as floor(conduit area × 0.45 ÷ cable area).

4

Derating for grouped cables

Meeting the 45% fill rule does not automatically mean the cables are correctly rated for their loads. BS 7671 Table 4C1 requires grouping correction factors to be applied to the current-carrying capacity of cables sharing a conduit: two circuits (Cg = 0.80), three circuits (Cg = 0.70), four circuits (Cg = 0.65), five circuits (Cg = 0.60), six or more circuits (Cg = 0.57). Always verify cable selection after applying these factors.

WORKED EXAMPLE

Six 2.5mm² single-core cables in a 20mm conduit

An electrician is running six 2.5mm² single-core PVC cables through a 20mm conduit. He needs to check whether this exceeds the 45% fill rule.

20mm conduit CSA

201 mm²

2.5mm² cable OD 6.6mm → area

34.2 mm²

6 cables total area

205 mm²

Fill = 205 ÷ 201 × 100

102% ✗

Assessment outcome

Upsize to 32mm conduit

32mm conduit (572mm²) gives 35.9% fill for 6 cables — compliant and easy to draw

Cable OD values are approximate. Always verify against the actual cable manufacturer's data sheet before finalising conduit selection.

Next step

Turn these figures into a professional PDF quote or invoice — free, no account needed to start.

FAQ

Frequently asked questions

Common questions about conduit fill, BS 7671 rules, and cable derating.

What is the 45% conduit fill rule?

BS 7671 (18th Edition Wiring Regulations) limits the total cross-sectional area of cables inside a conduit to 45% of the conduit's internal cross-sectional area. This limit applies where cables need to be drawn in or replaced after installation — it ensures enough room to pull cables through without damaging their insulation. The 45% rule is for three or more cables; for two cables the limit is 30%, and for a single cable it is 53% of the conduit bore. This calculator uses the 45% limit as the standard for multiple cables.

Why does conduit fill matter for heat dissipation?

Cables generate heat when carrying current (I²R losses). When cables are bunched inside a conduit, their combined heat cannot dissipate as efficiently as cables clipped singly to a wall. BS 7671 requires derating of current-carrying capacity when cables are grouped — typically reducing the rated capacity by 0.6–0.8 for common grouping arrangements (Appendix 4, Table 4C1). Overfilled conduits both reduce mechanical protection (more force needed to pull) and increase thermal stress on insulation, shortening cable life.

Can you mix cable sizes in the same conduit?

Yes — BS 7671 permits mixed cable sizes in the same conduit, provided the total cable area still complies with the 45% fill rule. However, mixing sizes creates practical problems: different cables have different pulling tensions, so the smaller cables may be damaged during installation. Grouping derating must be applied to all cables collectively, which often means the smaller cables become the limiting factor. In practice, electricians often prefer to run separate conduits for significantly different cable sizes.

What is the difference between conduit fill and trunking fill?

Conduit fill is calculated as a percentage of the conduit's circular cross-sectional area, with a 45% limit. Trunking fill is calculated as a percentage of the trunking's rectangular cross-sectional area, but the permitted fill percentage differs: BS 7671 Table 5A gives space factors for trunking depending on the number of cables. For trunking containing single-core cables, the fill factor is typically 45% for three or more circuits, the same as conduit. However, trunking is generally easier to fill and change than conduit because it has removable covers rather than requiring cables to be drawn through.

What is cable derating in conduit?

Cable derating is the reduction of a cable's current-carrying capacity (Iz) when it is installed in conditions worse than the BS 7671 reference method (typically single cable in free air or clipped to a surface). When multiple cables share a conduit, the grouping correction factor (Cg) from BS 7671 Table 4C1 applies. For example, two circuits in conduit: Cg = 0.8 (80% of the single-cable rating). Three circuits: Cg = 0.7. Four circuits: Cg = 0.65. Six or more: Cg = 0.57. These factors reduce the maximum permissible current and therefore the maximum load that can be connected.

What are BS 7671 conduit installation rules?

BS 7671 Section 522 covers protection against mechanical damage and conduit installation. Key requirements: conduit internal diameter must be at least 1.5 times the outside diameter of the cable with the largest diameter; conduit ends must be reamed smooth to prevent cable damage; conduit must be installed with draw-in boxes at sufficient intervals for pulling (typically every 5–8 metres on a straight run or after two 90° bends); conduit must be of suitable type for the environment (PVC conduit is not suitable for temperatures above 60°C or where mechanical impact is likely — use steel conduit); all joints must be waterproof if the conduit is installed in a damp location.